Question 1
At a pre-start check for Class I asbestos removal, an 18,000-ft³ negative-pressure enclosure is served by a HEPA exhaust unit rated at 1,500 ft³/min. With the filters and ductwork installed, measured exhaust is 900 ft³/min. Pressure is −0.03 inch water relative to the adjacent space. How should the supervisor evaluate these ventilation readings under OSHA's construction asbestos standard?
Show answer & explanation
Correct answer: C - 3 air changes per hour; increase delivered exhaust before removal.